Safe Mode is active
Symptom: sensor.pumpsteer attribute mode reads safe_mode. The fake
temperature equals the real outdoor temperature.
Cause: One or more required inputs are missing or invalid.
Diagnosis: Check the status attribute of sensor.pumpsteer — it contains the
specific reason, e.g.:
safe_mode: Missing sensors: indoor sensor 'sensor.indoor_temp' not configured
safe_mode: No price data from today='sensor.elpris_spot_avgifter', tomorrow='...'
Common fixes:
| Reason in status | Fix |
|---|---|
| Indoor or outdoor sensor missing | Check that the entity ID in the options flow still exists and is available |
| No price data | See Price sensor not working below |
Sensor state is unknown or unavailable |
Wait for HA to fully start; sensors recover automatically |
Safe mode resolves itself as soon as valid data is available. No restart needed.
Price sensor not working
Symptom: Safe mode due to missing price data, or price_category is always normal.
Diagnosis: PumpSteer accepts these list attributes on the configured electricity price entities:
todayorraw_today— today’s pricestomorroworraw_tomorrow— tomorrow’s prices used for lookahead
Each item must be a dict with a value or price key, or a plain number:
{ "value": 0.95 }
{ "price": 1.23 }
0.95
Check in Developer Tools → States:
- Find your price entity (e.g.
sensor.elpris_spot_avgifter) - Expand attributes
- Verify
todayorraw_todaycontains a list with usable numeric prices
If neither supported attribute exists, your price integration may use a different
format. Check the integration’s documentation. PumpSteer accepts plain numbers and
objects with a numeric value or price field.
PumpSteer supports both hourly (24 slots/day) and 15-minute (96 slots/day) price intervals. The interval is detected automatically from the price data.
Braking never occurs
Symptom: Price is expensive but mode stays normal and the fake temperature
does not rise.
Possible causes:
-
Comfort floor is preventing braking or pre-braking The indoor temperature is below the comfort floor (
target − allowed_drop). This blocks a new pre-brake and releases an existing brake/pre-brake ramp. Checkcomfort_floor_cinsensor.pumpsteerattributes. Lower aggressiveness or raise target temperature. -
Price is not classified as expensive P80 threshold may be higher than today’s peak price. Check
p80attribute onsensor.pumpsteer. If all prices are below P80, no slot is classified as expensive. Also check thatABSOLUTE_CHEAP_LIMIT(default 0.50 SEK/kWh) is not making all slots cheap — this triggers when P80 itself is below the limit. -
Aggressiveness is 0 All price logic is disabled at level 0. Raise saving level to at least 1.
-
Brake ramp has not completed yet Check
brake_factorin sensor attributes. If it is between 0 and 1, the ramp is still building up. This is normal — the ramp takesramp_inminutes.
Brake factor remains active after the price drops
Symptom: Price is no longer expensive, but the brake factor remains above zero or
the mode changes to brake_hold.
Possible causes:
-
Short-dip bridge is active PumpSteer holds the current brake factor only when the next expensive period starts within
BRAKE_HOLD_MINUTES(default 30 min). If the next expensive period is farther away, the brake should ramp out immediately. -
Next slot is also expensive Check the
price_categoryof upcoming slots. If the next slot is also expensive, the brake remains active. -
bridge_short_dipis active If an expensive period is coming within the configured bridge window, PumpSteer preserves the current brake factor across the short dip. The factor should stay flat, not continue ramping upward. Checkbridge_short_dip,minutes_until_expensive, andbridge_limit_minutesin the sensor attributes.
Wrong price category
Symptom: Current price seems wrong for the hour (e.g. classified as expensive when prices are low).
Cause: Price thresholds are cached once per calendar day and do not change mid-day. This is intentional — it prevents brake release during an ongoing expensive period due to threshold drift.
If thresholds seem clearly wrong:
- Check
p30andp80attributes onsensor.pumpsteer - Compare with today’s actual price spread
- Thresholds refresh at midnight when new price data arrives
P30/P80 thresholds are intentionally computed from today’s price list only. Tomorrow prices are used for lookahead decisions, not for changing today’s cached classification thresholds.
Preheat boost never triggers
Symptom: Switch is on, upcoming expensive slots exist, but mode never becomes preheating.
Diagnosis steps:
-
Check the thermal headroom. Preheat can continue slightly above target, but the boost tapers to zero at
target + preheat_headroom_c. Checkpreheat_headroom_c,preheat_ceiling_c, andpreheat_headroom_factoronsensor.pumpsteer. At a headroom factor of 0.0, extra preheat is intentionally blocked. -
Check
sensor.pumpsteer_thermal_outlook. When ThermalOutlook is available,preheat_worthwhilemust be true andpreheat_strengthscales how much boost is used. If ThermalOutlook cannot be built, PumpSteer falls back to the simpler_forecast_is_cold()check. -
Check that valid future price data exists. Preheat only runs when an expensive period is inside the configured lookahead. Tomorrow data is needed when that period crosses into the next day.
-
Check that
switch.pumpsteer_preheat_boostis on.
The maximum preheat headroom is 0.3 / 0.5 / 0.7 / 1.0 / 1.5 °C for saving levels 1 through 5 respectively.
Fake temperature seems too extreme
Symptom: sensor.pumpsteer state is at or near MIN_FAKE_TEMP or MAX_FAKE_TEMP.
During normal mode: A very low fake temperature means the PI is demanding maximum heating — large error between target and indoor temperature. Check that your target temperature is not set unrealistically high. Give the integral time to stabilize (12–24 hours of operation).
During braking: The fake temperature rises to outdoor + BRAKE_DELTA_C. At very
cold outdoor temperatures (e.g. −15 °C), this may produce a fake temp around −5 °C,
which is correct behavior. The heat pump will still provide some heat at −5 °C.
HA restart causes a large brake ramp jump
Symptom: After a restart, brake_factor jumps to a high value immediately.
Cause: This should not happen with current code. The brake ramp state is persisted
via RestoreEntity and the ramp dt is capped at 60 seconds per step.
If you observe this: check that extra_restore_state_data is not returning None in
logs. This can happen if the entity failed to save state before the restart.
Ohmigo push not working
Symptom: sensor.pumpsteer updates correctly but Ohmigo value does not change.
Check these:
switch.pumpsteer_ohmigo_pushison- The Ohmigo entity ID in the options flow matches the actual entity
- At least
ohmigo_interval_minuteshave passed since the last Ohmigo command - Changes smaller than 0.2 °C are treated as an unchanged setpoint, but the current setpoint is still resent when the interval is due to keep the Ohmigo watchdog alive
Check HA debug logs for Ohmigo push or Ohmigo keepalive resend messages to confirm commands are occurring.
Ohmigo Relay Guard does not recover the relay
Symptom: A configured Active/Bypass relay is off, but Relay Guard does not turn it on.
Check these gates:
switch.pumpsteer_ohmigo_relay_guardisonswitch.pumpsteer_ohmigo_push(Ohmigo Push) is explicitlyon- The configured relay explicitly reports
off
If the relay is unknown, unavailable or missing, Relay Guard intentionally sends
no command. This fail-closed behavior avoids guessing the state of the physical signal
path.
When recovery is eligible, Relay Guard waits briefly for state stabilization, then
tries switch.turn_on at most three times. A service call is not considered success
until the relay itself reports on.
Inspect the Relay Guard switch attributes for:
statusrelay_stateohmigo_push_staterecovery_attemptslast_recoverylast_failure
safe_mode alone does not inhibit Relay Guard. Ohmigo may still be forwarding the
real outdoor temperature, so the Active path can still be required.
Useful Developer Tools queries
In Developer Tools → Template, you can inspect PumpSteer state directly:
# Current mode and fake temperature
# Thermal outlook
PumpSteer diagnostic log files
PumpSteer writes a structured diagnostic log to:
/config/pump.log
The log is diagnostic only. PumpSteer does not read log entries back into the
controller and does not use pump.log for PI control, price braking, preheat decisions,
or ThermalModel calculations. Deleting old diagnostic logs therefore does not change
control behavior.
Current versions do not use a /config/pumplog/ directory. If such a directory exists,
it is legacy data from an older setup and can be removed.
Log rotation is simple: when PumpSteer initializes, a pump.log larger than 1 MB is
renamed to pump.log.1, replacing any older pump.log.1 file.
Old rotated logs and legacy pumplog files can be deleted at any time. Avoid deleting
the active /config/pump.log while Home Assistant is running, because PumpSteer may
still have the file open. If the active file is removed, perform a full Home Assistant
restart to ensure a new pump.log is created and logging resumes normally.
Enabling debug logging
Add this to your configuration.yaml to get detailed PumpSteer logs:
logger:
default: warning
logs:
custom_components.pumpsteer: debug
Reload the Logger integration (or restart HA), then check Settings → System → Logs. PumpSteer will log PI calculations, mode transitions, price threshold computations, brake ramp updates, and Ohmigo push events.
Safety reminder
Heating is a critical system. In safe mode PumpSteer passes through the real outdoor temperature when that sensor is still available, so the heat pump can continue on its own heating curve. If the outdoor sensor itself is unavailable, PumpSteer’s output is also unavailable. Monitor the system after installation and configuration changes.